We provide a complete line of general products and services to assist you with exit and emergency lighting, fire hoses, signs, flammable liquid cabinets and other safety related products.
| 1. |
|
Ensure the emergency lighting equipment is in its designated place. |
| 2. |
|
Inspect the housing for physical damage. |
| 3. |
|
Push test switch for 30 seconds. |
| 4. |
|
Verify lamps are illuminated and aimed in the correct direction. |
| 5. |
|
Maintain the monthly log for inspection by the authority having jurisdiction (AHJ). |
| 1. |
|
Conduct a thorough examination of the unit. |
| 2. |
|
Conduct an operational test of the battery and lighting system for the required 90 minutes. |
| 3. |
|
Check condition and voltage of the battery and verify manufacturer date. |
| 4. |
|
Check AC/DC lamps or bulbs for damage and proper operation. |
| 5. |
|
Verify charging circuit is operational and working properly. |
| 6. |
|
Apply emergency lighting test label to each light upon completion. |
|
 |
 |
|
 |